General fan performance notes:

1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static

pressure caused by any FIOPs or accessories.

3. Tabular data accounts for pressure loss due to clean filters, high gas heat, unit casing, and wet coils. Factory options

and accessories may add static pressure losses, as shown in the table above. Selection software is available, through

your salesperson, to help you select the best motor/drive combination for your application.

4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would

work, Bryant recommended the lower horsepower option.

5. For information on the electrical properties of Bryant motors, please see the Electrical information section of this

book.

6. For more information on the performance limits of Bryant motors, see the application data section of this book.