14. Relay Contacts and Inhibit Input

The DC-UPS is equipped with relay contacts and signal inputs for remote monitoring and controlling of the unit.

Relay contacts:

Ready:

Contact is closed when battery is charged more than 85%, no wiring failure is recognized, input

voltage is sufficient and inhibit signal is not active.

Buffering:

Contact is closed when unit is buffering.

Replace Battery:

Contact is closed when the unit is powered from the input and the battery quality test (SOH test)

reports a negative result.

Relay contact ratings

max

60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load

min

1mA at 5Vdc min.

Isolation voltage

max

500Vac, signal port to power port

Signal input:

Inhibit:

The inhibit input disables buffering. In normal mode, a static signal is
required. In buffer mode, a pulse with a minimum length of 250ms is
required to stop buffering. The inhibit is stored and can be reset by
cycling the input voltage. See also section 27.3 for application hints.

7

+

5.1V

3mA

Inhibit

8

-

Signal voltage

max.

35Vdc

Signal current

max.

6mA, current limited

Inhibit threshold

min.

6Vdc, buffering is disabled above this threshold level

max.

10Vdc

Isolation

nom.

500Vac, signal port to power port