All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM013A-EN-P — March 2014

5

Bulletin 1606 Switched Mode Power Supplies

6. Output in Normal Mode

Output voltage in normal mode

nom.

DC 24V

The output voltage follows the input voltage reduced by
the input to output voltage drop.

Voltage drop between input and
output

max.

0.3V

At 10A output current, see Fig. 6-1 for typical values

max.

0.45V

At 15A output current, see Fig. 6-1 for typical values

Ripple and noise voltage

max.

20mVpp

20Hz to 20MHz, 50Ohm *)

Output current

nom. 15A

Continuously

allowed

Output power

nom. 360W

Continuo usly

allowed

Short-circuit current

min.

17.9A

Load impedance 100mOhm, see Fig. 6-2 for typical values

max.

21A

Load impedance 100mOhm, see Fig. 6-2 for typical values

Capacitive and inductive loads

No

limitation

) This figure shows the ripple and noise voltage which is generated by the DC-UPS. The ripple and noise voltage

might be higher if the supplying source has a higher ripple and noise voltage.

Fig. 6-1

Input to output voltage drop, typ.

Fig. 6-2

Output voltage vs. output current in

normal mode at 24V input, typ.

Input to Output
Voltage drop

0

0

2

10

0.1

0.15

0.25

18A

0.05

0.2

0.3

0.35

0.4V

Output Current

4

6

8

12 14 16

Output Voltage

0

0

5

10

15

20

4

8

12

28V

16

20

24

25A

Output Current

Advertising