Front side user elements, Cd e – Rockwell Automation 1606-XL240-UPSE Power Supply Reference Manual User Manual

Page 12

Advertising
background image

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

12

Rockwell Automation Publication 1606-RM013A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

15. Front Side User Elements

A

Power Port

Quick-connect spring-clamp terminals, connection for input voltage,
output voltage and battery

B

Signal Port

Plug connector with sc

rew terminals, inserted from the bottom.

Connections for the Ready, Buffering, Replace Battery contacts and for
the Inhibit input. See details in section 14.

.

C

Green Status LED

Ready: Battery is charged > 85%, no wiring failure is recognized, input

voltage is sufficient and inhibit signal is not active.

Charging:

Battery is charging and the battery capacity is below 85%.

Buffering:

Unit is in buffer mode.

Flashing pattern of the green status LED:

Ready

1
0

1
0

Charging

1
0

Buffering

D

Yellow Diagnosis LED

Overload:

Output has switched off due to long overload in buffer mode

or due to high temperatures.

Replace battery:

Indicates a battery that failed the battery quality test (SoH test).

Battery should be replaced soon.

Inhibit active:

Indicates that buffering is disabled because of an active inhibit signal.

Flashing pattern of the yellow diagnosis LED:

1
0

Overload

1
0

Replace

Battery

1
0

Inhibit

active

E

Red Check Wiring LED

This LED indicates a failure in the installation (e..g. input voltage excessively low), wiring, battery or battery fuse.

F

Battery Temperature Selector

A: Same as this unit Temperature compensated end-of-charge voltage.
B: 10°C lower than this unit Temperature compensated end-of-charge voltage with an offset conditional upon tempera

C: 20°C lower than this unit Temperature compensated end-of-charge voltage with an offset conditional upon tempera

D: Battery temperature is 30°C

Fixed end of charge voltage for 30°C battery temperature

E: Battery temperature is 20°C

Fixed end of charge voltage for 20°C battery temperature

F: Battery temperature is 10°C

Fixed end of charge voltage for 10°C battery temperature

C

D

E

Advertising