Dc-ups control unit, Description, Specification quick reference – Rockwell Automation 1606-XL240-UPSE Power Supply Reference Manual User Manual

Page 2: Catalog numbers, Certification marks

Advertising
background image

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

2

Rockwell Automation Publication 1606-RM013A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

DC-UPS Control Unit

Requires Only One 12V Battery for a 24V Output

Allows Batteries Between 17Ah and 130Ah

Battery Charging with Temperature Tracking

Stable Output Voltage in Buffer Mode

Superior Battery Management for Longest Battery Life

Comprehensive Diagnostic and Monitoring Functions

Replace Battery Signal Included

Electronically Overload and Short Circuit Protected

50% Power Reserves

3 Year Warranty

1. Description

2. Specification Quick Reference

Input voltage

nom. 24Vdc

range

22.5-30Vdc

Output current

min.15A

Normal mode

min. 10A

Buffer mode

Output voltage

typ. 0.23V lower
as input voltage

Normal mode

22.25V

Buffer mode, 10A

Allowed batteries

17Ah to 130Ah

VRLA lead acid

Temperature range

-25 to +50°C

Dimensions 49x124x117mm

WxHxD

Buffer time (at 10A)

typ. 55 minutes

26Ah battery

typ. 4 hours

100Ah battery

This uninterruptible power supply (UPS) controller
1606-XLS240-UPSE is an addition to standard 24V
power supplies to bridge power failures or
emergency systems which must be kept fully in
operation for e.g. 72 hours.
The DC-UPS includes an internal temperature sensor
and a professional battery management system
which charges and monitors the battery to achieve
the longest battery service life as well as many
diagnostic functions that ensure a reliable operation
of the entire system.
A unique feature of the 1606-XLS240-UPSE is that only
one 12V battery is required to buffer the 24V
output.

This makes matching batteries unnecessary

and allows a precise battery charging and testing.

1606-XLS240-UPS

1606-XLS240-UPSD

1606-XLS240-UPSC

1606-XLS240-UPSE

battery

included

1606-XLS240-UPS Series

Related products

larger

battery sizes

additional

12V output

Typical setup of a DC-UPS system:

24V

Power

Supply

12V

Battery

24V

DC-UPS

24V

Load

AC

e.g.:

DC

e.g.: PLC

3. Catalog Numbers

4. Certification Marks

DC UPS

1606-XLS240-UPSE

Controller

Accessories 1606-XLSBAT2

Battery module 12V 26Ah

1606-XLSBATBR23

Mounting kit w/o battery

IND. CONT. EQ.

UL 508

UL 60950-1

EMC, LVD

1606-XLB

Panel/Wall mount bracket

UL 508

Marine

Marine RINA

GOST R

C-Tick