Rockwell Automation 1606-XL240-UPSE Power Supply Reference Manual User Manual

Page 14

Advertising
background image

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

14

Rockwell Automation Publication 1606-RM013A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

18. EMC

The unit is suitable for applications in industrial environments as well as in residencial, commercial and light industry
environment without any restrictions. The CE Mark indicates conformance with EMC guideline 89/336/EC, 93/68/EC and
2004/108/EC and the low-voltage directive (LVD) 73/23/EC, 93/68/EC and 2006/95/EC.

A detailed EMC report is avalaible upon request.

EMC Immunity

EN 61000-6-1, EN 61000-6-2 Generic standards

Electrostatic discharge

EN 61000-4-2

Contact discharge
Air discharge

8kV
15kV

Criterion A*)
Criterion A*)

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Out- and Input lines
Signal lines **)

2kV
2kV

Criterion A
Criterion A

Surge voltage

EN 61000-4-5

+ -

500V
500V

Criterion A
Criterion A

+ - housing

500V

Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

10V

Criterion A

*) DIN rail earthed
**) Tested with coupling clamp.


EMC Emission

EN 61000-6-3 and EN 61000-6-4 Generic standards

Conducted emission

EN 55022

Input lines

Class B*)
Class B*)

Radiated emission

EN 55011, EN 55022

Class B

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

*)

Informative measurement with voltage probe


Switching frequency

The DC-UPS has three converters with three different switching frequencies included.

Switching

frequency

of

boost

converter

100kHz

Constant

frequency

Switching frequency of electronic output current limitation

78kHz

Constant frequency

Switching frequency of battery charger

19.5kHz

Constant frequency

Output

Input + -

EN 55022

Output lines

Advertising