All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM013A-EN-P — March 2014

15

Bulletin 1606 Switched Mode Power Supplies

19. Environment

Operational temperature

-25°C to +50°C

Full power, for the DC-UPS control unit.
Keep battery in a cooler environment!

Storage

temperature

-40 to +85°C

Storage and transportation, except battery

Humidity

5 to 95% r.H.

IEC 60068-2-30
Do not energize while condensation is present

Vibration sinusoidal

2-17.8Hz: ±1 .6mm; 17.8-500Hz: 2g

IEC 60068-2-6

Shock

30g

6ms,

20g

11ms

IEC

60068-2-27

Altitude

0 to 6000m

Approvals apply only up to 2000m

Over-voltage category

III

EN 50178

II

EN 50178 above 2000m altitude

Degree of pollution

2

EN 50178, not conductive

Fig. 19-1 Output current vs. ambient temperature

Fig. 19-2 Output current vs. ambient temperature

Allowable Output Current in Normal Mode

0

-25

0

20

30

50°C

2.5

5

7.5

10

12.5

15A

40

10

Ambient Temperature

Allowable Output Current in Buffer Mode

0

-25

0

20

30

50°C

2.5

5

7.5

10

12.5

15A

10

40

Ambient Temperature

continuous

for typ. 5s

The ambient temperature is defined 2cm below the unit.

20. Protection Features

Output protection

Electronically protected against overload, no-load and short-circuits

Output over-voltage protection

in buffer mode

typ. 32Vdc
max. 35Vdc

In case of an internal defect, a redundant circuitry
limits the maximum output voltage. The output
automatically shuts-down and makes restart attempts.

Degree of protection

IP20

EN/IEC 60529

Penetration protection

> 3.5mm

E.g. screws, small parts

Reverse battery polarity protection

yes

Max. –35Vdc;

Wrong battery voltage protection

yes

Max. +35Vdc (e.g. 24V battery instead of 12V battery)

Battery deep discharge protection

yes

The limit is battery current dependent

Over temperature protection

yes

Out put shut-down with automatic restart

Input

over-voltage

protection

yes

Max. 35Vdc, no harm or defect of the unit

Internal input fuse

25A, blade type

No user accessible part, no service part