Rockwell Automation Publication 1608M-UM003A-EN-P - April 2014

23

Operation

Chapter 5

Automatic Bypass
Switchboard Operating
Instructions

Automatic System

Bypass (CBB) will close in the event of a fault in the MegaDySC system. System
will remain in bypass until manually transferred to back to the MegaDySC. If
CBB trips due to an over current condition, press reset button on CBB. CBB will
automatically close!

Manual Transfer to Maintenance Bypass

1.

Press green “CLOSE CBB” push button

2.

Confirm that red “BYPASS CLOSED” lamp is lit.

3.

Press red “OPEN CBI” push button. Output breaker (CBO) will open
automatically.

4.

Confirm that both CBI and CBO are open.

5.

The MegaDySC is now bypassed and isolated for maintenance.

Manual Transfer to MegaDySC

1.

Confirm green "READY TO CLOSE CBI" lamp is on.

2.

Manually close breaker CBI.

3.

Confirm that the MegaDySC touchscreen is lit, is green and displays
“OK” in the upper left corner.

4.

Manually close breaker CBO.

5.

Confirm that the screen on the MegaDySC displays “OK”.

6.

Press red “OPEN CBB” push button.

7.

The MegaDySC system is now providing power to the load.

ATTENTION: Follow these instructions to avoid interrupting load power!
Contact the factory immediately if the system fails to operate as outlined below.
Voltage sag protection is not available whenever CBB is closed (red lamp
lighted)

IMPORTANT

Close CBI is inhibited for one minute after power cycling.