Table 10 - system event table – Rockwell Automation 1608M MegaDySC User Manual, 208 Volt, One Second Extended Runt User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 1608M-UM004A-EN-P - April 2014

Chapter 7

Maintenance

Table 10 - System Event Table

Event Code

Code Name

Full Name

Severity

Area

Event Description

Event Resolution

1

POWER_ON

DySC Power On

Informational

Unit

Power re-applied to the DySC.

No action needed.

4

T_FAN_ST

Fan Test Start

Informational

Unit

Start acknowledgment of DySC fan test.

No action needed.

5

T_IN_ST_1

Inverter Test (.5 cycles) Start

Informational

Unit

Start acknowledgment of DySC 0.5 cycle
inverter test.

No action needed.

6

T_IN_ST_2

Inverter Test (3 cycles) Start

Informational

Unit

Start acknowledgment of DySC 3 cycle
inverter test.

No action needed.

7

T_IN_ST_3

Inverter Test (5.5 seconds) Start

Informational

Unit

Start acknowledgment of DySC 5.5
second inverter test.

No action needed.

9

EXTERNAL

External Inhibit

Auto-Resetting

Inverter

Controller is inhibited by another phase
controller.

Review event details from other phase controllers.

11

RUN_TO

Inverter Run Timeout

Auto-Resetting

Inverter

DySC inverter had a total cumulative
runtime of more than rated.

No action needed.

12

LIM_CYCLE

Inverter Limit Cycle Timeout

Auto-Resetting

Inverter

Power was re-applied more than once
within a 58 second period.

No action needed.

13

STAT_OT

Static Switch Over-Temperature

User Attention

Static
Switch

Static switch heatsink temperature was
greater than maximum rating.

Verify ambient temperature is within DySC
specification. Check for damaged fans. Check for
dirty or obstructed air filters.

14

OVERLOAD

Overload

User Attention

Unit

Inverter inhibited because load current
exceeded maximum rating.

Reduce load. In parallel DySC systems, verify proper
current sharing among slave cabinets.

15

DC_OV

DC Bus Over-Voltage

User Attention

Inverter

Positive or negative half of DC bus
voltage exceeded maximum rating.

Verify line voltage is within ratings. Verify proper
DySC application. Call service.

16

CNTRL_UV

Controller Power Under-Voltage

User Attention

Inverter

DySC control power supply is out of
tolerance.

Verify DySC is online and line voltage is within
ratings. Call service.

17

OUTPUT_UV

Output Under-Voltage

User Attention

Inverter

DySC output voltage was less than 80%
of nominal during sag correction. Sag
condition likely outside of DySC
specification.

Verify line voltage is within ratings. Verify proper
DySC application.

18

INV_OC

Inverter Over-Current

User Attention

Inverter

Inverter current exceeded maximum
rating during sag correction.

Verify load current is within ratings. Verify
mechanical bypass switch is open. Verify proper
DySC application.

19

DC_UV

DC Bus Under-Voltage

User Attention

Inverter

DC bus voltage below operational range.

Verify line voltage is within ratings. Call service.

20

OUTPUT_OV

Output Over-Voltage

Call Service

Inverter

DySC output voltage was greater than
115% of nominal during sag correction.

Call service.

22

IGBT

IGBT Pack

User Attention

Inverter

IGBT pack reported error. Possible sag
condition outside of DySC specification.

Verify line voltage is within ratings. Verify proper
DySC application. Call Service.

25

SYNC_ERR

Line Synchronization Error

Call Service

Inverter

Inverter not synchronized to line when
sag detected.

Call service.

31

CONFIG

Configuration Alert

Call Service

Inverter

Controller configuration has changed.

Call service.

32

CNTRL_MEM

Controller Memory Busy

Auto-Resetting

Inverter

Controller is loading new data into Flash
memory.

No action needed.

Advertising