Voltage sag rms voltage charts, Figure 21 - rms voltage charts, Voltage sag notification – Rockwell Automation 1608M MegaDySC User Manual, 208 Volt, One Second Extended Runt User Manual

Page 35: Figure 22 - voltage sag detected

Advertising
background image

Rockwell Automation Publication 1608M-UM004A-EN-P - April 2014

35

Display Screen

Chapter 6

Voltage Sag RMS Voltage

Charts

The line and load RMS voltage (L-N) of each phase is recorded for 8 cycles prior
to the start of the voltage sag followed by the first 300 cycles of the voltage sag
(See

Figure 21

). Reach this screen by pressing “CHARTS” on the “Voltage Sag

Detail” screen as shown in

Figure 20 on page 34

.

Figure 21 - RMS Voltage Charts

Line voltage is shown in red and load voltage is shown in green. By pressing the
check boxes in the right column, you can toggle each data series Off and On as
well as enable y-axis auto-scaling.

Note: 300 cycles = 5.0 seconds at 60 Hz or 6 seconds at 50 Hz.

Voltage Sag Notification

While the voltage sag is in-progress, a flashing red box in the upper left-hand
corner will display “SAG-IN-PROGRESS.” This box will appear on every screen
until the voltage sag ends. See

Figure 22

.

Figure 22 - Voltage Sag Detected