Open static switch (failure in static switch path), Open main input fuse (f1-f2-f3-f4-f5-f6), Over-temperature of static switch heatsink – Rockwell Automation 1608M MegaDySC User Manual, 208 Volt, One Second Extended Runt User Manual
Page 27: Over temperature of megadysc cabinet ambient air, Open cabinet door
Advertising
Rockwell Automation Publication 1608M-UM003A-EN-P - April 2014
27
Operation
Chapter 5
Open circuit alarm conditions:
1.
Open static switch (failure in static switch path)
2.
Open main input fuse (F1-F2-F3-F4-F5-F6)
3.
Overload of static switch (may cause over-current trip in CBI; see
Specifications)
4.
Over-temperature of static switch heatsink
5.
Over temperature of MegaDySC cabinet ambient air
6.
Open cabinet door
NOTE: Alarm types 1, 2, and 3 may result in momentary interruption of power to the load before
transferring to mechanical bypass. Types 4 through 6 will result in a seamless transfer to
mechanical maintenance bypass, without interruption.