Open static switch (failure in static switch path), Open main input fuse (f1-f2-f3-f4-f5-f6), Over-temperature of static switch heatsink – Rockwell Automation 1608M MegaDySC User Manual, 208 Volt, One Second Extended Runt User Manual

Page 27: Over temperature of megadysc cabinet ambient air, Open cabinet door

Advertising
background image

Rockwell Automation Publication 1608M-UM003A-EN-P - April 2014

27

Operation

Chapter 5

Open circuit alarm conditions:

1.

Open static switch (failure in static switch path)

2.

Open main input fuse (F1-F2-F3-F4-F5-F6)

3.

Overload of static switch (may cause over-current trip in CBI; see
Specifications)

4.

Over-temperature of static switch heatsink

5.

Over temperature of MegaDySC cabinet ambient air

6.

Open cabinet door

NOTE: Alarm types 1, 2, and 3 may result in momentary interruption of power to the load before
transferring to mechanical bypass. Types 4 through 6 will result in a seamless transfer to
mechanical maintenance bypass, without interruption.