Table 11 - megadysc fuse schedule, Main cabinet – Rockwell Automation 1608M MegaDySC User Manual, 208 Volt, One Second Extended Runt User Manual

Page 47

Advertising
background image

Rockwell Automation Publication 1608M-UM004A-EN-P - April 2014

47

Maintenance

Chapter 7

Table 11 - MegaDySC Fuse Schedule

IMPORTANT

A qualified electrician must replace the fuses. Open the front cabinet door(s) to
access the fuse holders and fuses.

To maintain protection of the MegaDySC, be sure to replace the fuse with the
same type and rating. These fuses are available through Rockwell Automation
Technical Support.

Fuse Reference

Fuse Location

Fuse Rating

Manufacturer

Manufacturer

Part Number

Rockwell

Automation

Cat. No.

MegaDySC Main Cabinet Fuses

F1, F2, F3, F4, F5, F6

Main Cabinet

Main Power Input

800 A/500V

Mersen

A50QS800-4IL

43-00042

F7, F8, F9

Inverter Input

F10, F11, F12 (200KVA)

Cross-Coupling Transformer

450 A/600V

AJT450

43-00112R

F10, F11, F12 (300KVA)

Cross-Coupling Transformer

500 A/600V

AJT500

43-00204R

F13, F14, F15

Series Injection Transformer

200 A/600V

AJT200

43-00017

F16, F17

Input Control Transformer

2 A/600V

ATQR2

43-00030

F18 - F29

Dynamic Brake

25 A/600V DC

ATM25

43-00094

F30, F31

Output Control Transformer

8 A/600V

TR8R

43-00115R

F32, F33, F34, F35, F36, F37

DC Bus

400 A/500V DC

A50QS400-4

43-00209R

EA4-F1

Ground Filter Assembly

20 A/600VDC

ATM20

43-00093

MegaDySC Power Module Fuses

F1, F2

Power
Module (x3)

Voltage Feedback

2 A/600V

Mersen

ATQR2

43-00030

F3

Inverter Output

400 A/500 V

A50QS400-4IL

43-00062

MegaDySC ER Cabinet Fuses

F1, F2

ER Cabinet

Main Power Unit

400 A /500V DC

Mersen

A50QS400-4IL

43-00062

F3, F4, F5, F6

Main SCRs

200 A /500V DC

A50QS200-4IL

43-00191R

F7, F8, F9

DC Voltage Feedback

2 A /600V DC

ATM2

43-00145R

Snub 1 - F1
Snub 2 - F1
Snub 3- F1
Snub 4- F1

SCR Snubber Assemblies

20 A /600V DC

ATM20

43-00093

PCB19-F1

Ground Filter Assembly

Advertising