592 overload relay, Reset relay/pushbutton, Surge suppressor – Rockwell Automation 1519 MV DRIVE HARMONIC FILTER PF CORRECTION UNIT User Manual

Page 12: Cooling fan, Strip heater and thermostat (optional)

Advertising
background image

 )." %. 0

2-2

Physical Layout and Component Identification

Component Identification

592 Overload Relay

and Functional Descriptions
(cont.)

A Bulletin 592 thermal overload relay is used to prevent an excessive current

condition in the reactor and capacitors. This is a manually reset, eutectic alloy-

type device. The ratchet stud assembly is heated by current flowing through

the heater element. Relay operation occurs when the temperature of the ratchet

stud reaches the melting point of the eutectic alloy, freeing the ratchet wheel

and opening the normally closed contact.

Reset Relay/Pushbutton

The reset relay is used to latch in a fault that occurs on the harmonic filter.

The reactor thermal switches, 592 overload contact, and SMP-3 relay contact

for a filter leg are wired in series with the reset relay. When one of these

devices operates the reset relay latches open until the individual device(s) are

reset and the reset pushbutton associated with the reset relay is depressed.

Surge Suppressor

Acts to reduce voltage transients associated with de-energization of a reset

relay coil.

Cooling fan

Each cabinet has two continuously running cooling fans each with a 550 CFM

capacity. They are supplied either 110/120 V or 220 V depending on the

control voltage available. The fans are oriented to blow air out of the top,

forward-facing vent.

Strip Heater and Thermostat (Optional)

Strip heaters are located in each cabinet for preventing condensation which

may occur if the cabinet temperature is lower than the ambient temperature.

They are available for either a 110/120 V or 220 V separate source.