Troubleshooting and Repair

Troubleshooting (cont.)

592 Thermal Overload Relay

If a 592 thermal overload relay has tripped this indicates that an excessive

current has occurred in the harmonic filter. An overload condition means that

the reactor and/or the capacitors in the filter have been subjected to a current

higher than they were designed for. Some investigation should be carried out

to determine why the overload occurred. An overload could occur if excessive

harmonic currents are present due to non-linear loads other than the drive it

was designed for. The heater element sizing should be confirmed with Rockwell

Automation to make sure that it coincides with the reactor current. Nuisance

tripping could result if the heater elements are undersized for the particular filter.

Component Replacement

If any damaged components are discovered, check your customized parts list

Instructions

or see Chapter 8 (Renewal Parts) to determine the appropriate replacement

part. See page 1 for parts supply contacts. Generally, all components are

easily accessible and simply require removal of cables and mounting hardware.

Make sure to label wire and cable terminations before disconnecting and

properly torque power connections when reassembling per page 5-1. The

following are some specific details to note regarding certain components:

ATTENTION:

Damaged components must be replaced with

those bearing the same part number or equivalent. Failure to use

correct replacement parts, or to follow the specified replacement

guidelines, may result in equipment damage or poor equipment

performance.

ATTENTION:

Ensure main power has been disconnected and

locked out before replacing any components. Verify with a hot

stick or meter that all circuits are voltage-free. Failure to do so

may result in electric shock causing severe burns, injury or death.

Current Transformers

The orientation is important for proper current sensing. Make sure the

replaced unit is physically oriented the same way as the others in the grouping

as indicated by the position of the control wire terminals. You will need to

disconnect the power cable associated with the particular current transformer at

one end as well as the control wires from the Bul. 592 overload relay in order

to remove the unit being replaced.