background image

 )." %. 0

6-2

Annual Inspection

Physical Inspection (cont.)

Components

Check all components for any signs of damage or overheating. Any

components displaying physical damage or severe discoloration should be

replaced (see Chapter 8). In particular, check the capacitors for ruptures and

make sure there is no leaking dielectric fluid.

Interlocks

Check for proper functioning of all door interlocks (clip type and key type).

They must prevent medium voltage doors from being opened if there is power

applied to the filter.

Foreign Material

Check for dust, dirt, iron filings etc. that may have entered the structure and

vacuum clean if necessary. In particular, check the cooling fans and vents to

make sure they are unobstructed.

Advertising