Commissioning

Pre-start-up Inspection (cont.)

• For future reference, record component data on the table below:

Table 5.A
Component Specifications

Fifth Filter

Seventh Filter

Eleventh Filter

Capacitor kVAR

(3) @

(3) @

(3) @

(3) @

Capacitor Farads

(3) @

(3) @

(3) @

(3) @

Reactor Amps

Reactor mH

Reactor Tap Connection

CT Ratio

(3) @

(3) @

(3) @

(3) @

O/L Elements

SMP-3 Setting (FLC)

Settings

The SMP-3 relay(s) are factory set to allow detection of a blown capacitor fuse

(phase loss detection). No adjustment should be required on the SMP-3 relay(s).

The overload elements are factory selected and installed to provide proper

overload protection. No adjustment should be required on the heater elements.

The reactor(s) are factory set on the nominal inductance tap. The reactor(s)

have ±5% taps to allow increasing or decreasing the inductance and thus

changing the tuned frequency of the filter.

In general, Rockwell Automation should be consulted when considering a

change to a reactor tap setting, SMP-3 setting or 592 heater elements.