Chapter 7 – troubleshooting and repair, Troubleshooting, Harmonic filter fault – Rockwell Automation 1519 MV DRIVE HARMONIC FILTER PF CORRECTION UNIT User Manual

Page 25: Smp-3 relay, Troubleshooting and repair, Chapter 7, Chapter

Advertising
background image

Chapter

7

1519-5.0 – May 1998

Troubleshooting and Repair

Troubleshooting

Annunciation and action in the event of a harmonic filter fault will vary

depending on the particular drive/harmonic filter system. If the drive input

starter is used as the harmonic filter switching device, then a harmonic filter

fault will have the effect of creating an external fault described as “HF FAULT”

(for Harmonic Filter Fault) on the associated drive. Any fault on the drive

results in opening of the associated input starter, which de-energizes the filter.

This Harmonic Filter Fault will be annunciated on the Panelview operator

terminal under “ALARMS”.

Harmonic Filter Fault

The contacts for reactor overtemperature, SMP-3 blown capacitor fuse

detection, and Bulletin 592 thermal overload are generally wired in series and

any one of these conditions can create a Harmonic Filter Fault. If a Harmonic

Filter Fault occurs then the SMP-3 relay(s) and 592 overloads should be

checked to see if they are in the tripped condition. Both the SMP-3 and the

592 are manually reset relays.

SMP-3 Relay

If an SMP-3 relay has tripped this generally indicates that one or more

capacitors in the harmonic filter have failed in a short-circuit condition. Reset

the SMP-3 relay by pressing its reset push button. For your safety, wait five

minutes before accessing the capacitors to allow them to discharge. Verify

with a hot stick and meter that the capacitors are voltage-free.

The fuses mounted on top of each of the capacitors associated with the tripped

SMP-3 relay should be checked with an ohmmeter for continuity. If a very

high resistance is seen on one or more fuses, this indicates that the fuse has

blown. It is also likely that the associated capacitor has failed. To check a

capacitor an ohmmeter can be connected to the capacitor terminals. If a

gradual change in resistance is seen on the meter then the capacitor is good. If

a very low resistance and no gradual change in resistance is seen this indicates

that the capacitor has shorted internally and must be replaced.

1519-IN050B-EN-P June 2013

Advertising