Filter reactors, Cooling fans, Capacitors and capacitor fuses – Rockwell Automation 1519 MV DRIVE HARMONIC FILTER PF CORRECTION UNIT User Manual

Page 27: Component replacement instructions (cont.)

Advertising
background image

1519-5.0 – May 1998

Troubleshooting and Repair

7-3

Filter Reactors

The mounting provision for the reactors is variable in the left-to-right direction.

There are sliding nuts under the mounting slots that may move while the

reactor is being removed. When the new reactor is placed in position, simply

slide the nuts into position with a screwdriver and reinstall the mounting bolts.

Make sure there is a minimum of 3 in. of clearance between reactors and

between any reactor and the cabinet. There are lifting channels on top of each

reactor suitable for forklifts that will accommodate a single fork for smaller

reactors and two forks for larger reactors. Make sure the capacity of the

forklift is sufficient before lifting reactors (the reactor weight is specified on

the nameplate).

Cooling Fans

When replacing cooling fans, make sure they are oriented in the proper

direction. The airflow direction is indicated by an arrow on the outside surface

of the fan housing and should be pointing outward (out through the door).

Also, make sure the leads are not reversed as this will reverse the fan rotation.

Capacitors and Capacitor Fuses

Before beginning any disassembly to replace capacitors, take note of the

jumper configuration and cable termination locations (i.e. wye or delta

configuration). When torquing connections on a capacitor terminal or on the

top of a fuse, remember to use only 10 ft-lb (13.5 N-m).

Component Replacement
Instructions (cont.)

1519-IN050B-EN-P June 2013

Advertising