All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

11

Bulletin 1606 Switched Mode Power Supplies

12. Terminals and Wiring

The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.

Input and output

DC-OK-Signal

Type

screw terminals

spring-clamp terminals

Solid wire

0.5-6mm

2

0.15-1.5mm

2

Stranded wire

0.5-4mm

2

0.15-1.5mm

2

American Wire Gauge

AWG20-10

AWG26-14

Max. wire diameter

2.8mm (including ferrules)

1.5mm (including ferrules)

Wire stripping length

7mm / 0.28inch

7mm / 0.28inch

Screwdriver

3.5mm slotted or cross-head No 2

3.5mm slotted (to open the spring)

Recommended tightening torque

1Nm, 9lb.in

not applicable

Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:

60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.

b

Follow national installation codes and installation regulations!

c)

Ensure that all strands of a stranded wire enter the terminal connection!

d) Do not use the unit without PE connection.
e) Unused terminal compartments should be securely tightened.
f)

Ferrules are allowed.

Daisy chaining:

Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 12-2.

Fig. 12-1 Daisy chaining of outputs

Fig. 12-2 Using distribution terminals

Load

+

-

Power

Supply

+ +

- -

Output

Power

Supply

+ +

- -

Output

max 25A!

continuous

Distribution

Terminals

Load

+

-

Power

Supply

+ +

- -

Output

Power

Supply

+ +

- -

Output