Environment – Rockwell Automation 1606-XLE480FP Power Supply Reference Manual User Manual

Page 14

Advertising
background image

All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

14

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

Switching Frequencies

The power supply has two converters with two different switching frequencies included.

Switching frequency 1

70kHz to 130kHz

PFC converter, input voltage and output power dependent

Switching frequency 2

80kHz to 140kHz

Main converter, output power dependent

15. Environment

Operational temperature

*)

-25°C to +70°C (-13°F to 158°F)

reduce output power according Fig. 15-1

Storage temperature

-40 to +85°C (-40°F to 185°F)

for storage and transportation

Output de-rating

6.4W/°C
12W/°C

45°C to 60°C (113°F to 140°F)
60°C to 70°C (140°F to 158°F)

Humidity

**)

5 to 95% r.h.

IEC 60068-2-30

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g

***)

2 hours / axis

IEC 60068-2-6

Shock

30g 6ms, 20g 11ms

***)

3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 2000m (0 to 6 560ft)

without any restrictions

2000 to 6000m (6 560 to 20 000ft)

reduce output power or ambient temperature,
see Fig. 15-2
IEC 62103, EN 50178, overvoltage category II

Altitude de-rating

30W/1000m or 5°C/1000m

> 2000m (6500ft), see Fig. 15-2

Over-voltage category

III

IEC 62103, EN 50178, altitudes up to 2000m

II

altitudes from 2000m to 6000m

Degree of pollution

2

IEC 62103, EN 50178, not conductive

LABS compatibility

The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.

Audible noise

At load currents below 1A some audible noise will be emitted from the power supply

*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize in the presence of condensation.
***) Higher levels allowed when using the 1606-XLC wall mounting bracket.

Fig. 15-1 Output current vs. ambient temp.

Fig. 15-2 Output current vs. altitude

Allowed Output Current at 48V

0

-25

0

20

40

70°C

2A

4A

6A

8A

10A

12A

60

B

A

Ambient Temperature

A...100 to 264Vac, continuous
B... 85Vac, continuous
C... Short term

C

0

0

2000m

4000m

6000m

2A

4A

6A

8A

10A

12A

B

A

C

A... Tamb < 60°C

B... Tamb < 50°C

C... Tamb < 40°C

D... Short term

D

Allowable Output Current at 48V

Altitude

See section 3 for derating requirements for input voltages between 85Vac and 100Vac.