Parallel use to increase output power, Parallel use for redundancy – Rockwell Automation 1606-XLE480FP Power Supply Reference Manual User Manual

Page 21

Advertising
background image

All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

21

Bulletin 1606 Switched Mode Power Supplies

22.5. Parallel Use to Increase Output Power

1606-XLE480FP power supplies can be paralleled to increase the output power.
The output voltage of all power supplies shall be adjusted to the same value
(±100mV) in “Single use” mode with the same load conditions on all units, or
the units can be left with the factory settings. After the adjustments, the
jumper on the front of the unit shall be moved from “Single use” to “Parallel
use”, in order to achieve load sharing. The “Parallel use” mode regulates the
output voltage in such a manner that the voltage at no load is approx. 4%
higher than at nominal load. See also section 6. If no jumper is plugged in, the
unit is in “Single use” mode. Factory setting is “Single use” mode.
If more than three units are connected in parallel, a fuse or circuit breaker
with a rating of 15A or 16A is required on each output. Alternatively, a diode or redundancy module can also be
used.

Unit A

AC

DC

Unit B

AC

DC

-

+

-

+

Load

+

-

Energize all units at the same time to avoid the overload Hiccup

PLUS

mode. It also might be necessary to cycle the input

power (turn-off for at least five seconds), if the output was in Hiccup

PLUS

mode due to overload or short circuits and the

required output current is higher than the current of one unit.

Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power
supplies on top of each other. Do not use power supplies in parallel in mounting orientations other than the standard
mounting orientation (terminals on bottom of the unit) or in any other condition where a derating of the output
current is required (e.g. altitude, above 60°C, …).

Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.

22.6. Parallel Use for Redundancy

Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a
certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two
power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is
automatically able to support the load current without any interruption. Redundant systems for a higher power
demand are usually built in a N+1 method. E.g. five power supplies, each rated for 10A are paralleled to build a 40A
redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also section
22.5.

Recommendations for building redundant power systems:

a)

Use separate input fuses for each power supply.

b)

Set the power supply into “Parallel use” mode.

c)

Monitor the individual power supply units. Therefore, use the DC-OK relay contact of the power supply.

d)

It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting.

Advertising