All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

12

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

13. Front Side and User Elements

Fig. 13-1 Front side

A Input

Terminals

(screw terminals)

N,

L

Line input

PE (Protective Earth) input


B Output

Terminals

(screw terminals, two pins per pole)

+

Positive output

– Negative (return) output


C Output voltage potentiometer

Open the flap to adjust the output voltage. Factory set: 48.0V


D DC-OK

LED

(green)

On, when the output voltage is >90% of the adjusted output voltage


E DC-OK

Relay

Contact

(quick-connect spring-clamp terminals)

The DC-OK relay contact is synchronized with the DC-OK LED.
See section for details.


F “Parallel Use” “Single Use” selector

Set jumper to “Parallel Use” when power supplies are connected in parallel
to increase the output power. In order to achieve a sharing of the load
current between the individual power supplies, the “parallel use” regulates
the output voltage in such a manner that the voltage at no load is approx.
4% higher than at nominal load. See also section 24.5. A missing jumper is
equal to a “Single Use” mode.