All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

8

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

AC 100V

AC 120V

AC 230V

Hold-up Time

typ.

65ms

65ms

65ms

at 48V, 5A, see Fig. 7-1

min.

54ms

54ms

54ms

at 48V, 5A, see Fig. 7-1

typ.

26ms

26ms

26ms

at 48V, 10A, see Fig. 7-1

min.

21ms

21ms

21ms

at 48V, 10A, see Fig. 7-1

Fig. 7-1 Hold-up time vs. input voltage

Fig. 7-2 Shut-down behavior, definitions

0

10

20

30

40

80ms

90

120

155

190

230Vac

Input Voltage

50

60

Hold-up Time

48V, 10A, typ.

48V, 5A, min.

48V, 5A, typ.

70

48V, 10A, min.

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input
Voltage


8. DC-OK Relay Contact


This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed
voltage from a unit connected in parallel to the power supply output.

Contact closes

As soon as the output voltage reaches 90% of the adjusted output voltage level.

Contact opens

As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.

Contact ratings

max.

60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A

resistive load

min.

1mA at 5Vdc

min. permissible load

Isolation voltage

See dielectric strength table in section 18.

Fig. 8-1 DC-ok relay contact behavior

100ms

0.9* V

ADJ

<

1ms

10%

open

V

OUT

= V

ADJ

open

closed

closed

>

1ms