16 ControlLogix Remote I/O (RIO) Module

Rockwell Automation Publication 1756-IN610B-EN-P - November 2010

Wire the Connector for the Remote I/O Network

To wire the connector for the remote I/O network, refer to the Cabling and
Termination table and follow these steps.

1.

Connect Line 1 (blue) of the remote I/O cable to the lower pin on the
1756-RIO module.

2.

Connect the shield to the middle pin.

3.

Connect Line 2 (clear) of the remote I/O cable to the upper pin on the
1756-RIO module.

4.

Terminate both ends of a remote I/O network by using external resistors
attached to the physical ends of the network.

There should be two terminators at the ends network. The terminator is
connected between Line 1 (blue) and line 2 (clear).

Cabling and Termination

Connector Pin

Description

1 (bottom)

Line 1 (blue)

N/A

Shield

2

Line 2 (clear)