Ok status indicator – module health, Interpret the alphanumeric display – Rockwell Automation 1756-RIO ControlLogix Remote I/O (RIO) Communication Interface Module Installation Instr User Manual

Page 21

Advertising
background image

ControlLogix Remote I/O (RIO) Module 21

Rockwell Automation Publication 1756-IN610B-EN-P - November 2010

OK Status Indicator – Module Health

Interpret the Alphanumeric Display

The remote I/O (RIO) communication interface module displays alphanumeric
messages that provide diagnostic information about your module. The warning
messages appear twice on the display, then the normal display resumes. The table
summarizes the messages.

Indicator

Status

Description

OK

Green

Indicates that module has passed all power-up
diagnostics and is functioning normally.

Red

Indicates that module start-up diagnostics have
failed or a major module fault, such as watchdog
time-out or jabber inhibit, has occurred.

IMPORTANT

If all three status indicators are solid red and the 4-character
display shows M#xx, (where xx is the error number), a fatal
error has occurred. Refer to the 1756-RIO user manual,
publication

1756-UM534

, for information on clearing fatal

errors. Make a note of the error code numbers to give
Technical Support, if you need to call for help.

Alphanumeric Display Message Descriptions

Message

Description

RIO Scanner v. x.xx.xx [banner]
RIO Adapter v. x.xx.xx [banner]

The module’s firmware revision, displayed at powerup.
The three parts of the revision number are the major
revision, the minor revision, and the build number. This
is followed by the status banner.