Rockwell Automation Publication 1756-IN610B-EN-P - November 2010

Module Status Indicators

The module has three status indicators to indicate the state of internal
operations. The status indicators are labeled RIO, CLX, and OK.

RIO Status Indicator – Remote Devices Status

The RIO indicator displays the status of the remote I/O network connection.
Status varies depending on the mode of the module.

Scanner Mode

This table shows status in order of priority, highest first.

Indicator

Status

Description

RIO

Red

A frame-receive error has been received in the last
second (CRC error, abort, or time-out). Indicator stays
red for one second after the error occurs.
One or more racks are in error.

Flashing red/off

At least one rack that is being scanned (not inhibited)
is in error. One or more racks are inhibited.

Yellow

Idle, no racks are configured.

Flashing yellow/off

All configured racks are inhibited.

Flashing green/off

No racks being scanned (not inhibited) are in error, but
one or more racks are inhibited.

Green

Successful communication with all configured racks,
no inhibited racks.

44777

RIO CLX OK

Advertising