About the module, 1756-rio module as a scanner – Rockwell Automation 1756-RIO ControlLogix Remote I/O (RIO) Communication Interface Module Installation Instr User Manual

Page 7

Advertising
background image

ControlLogix Remote I/O (RIO) Module 7

Rockwell Automation Publication 1756-IN610B-EN-P - November 2010

About the Module

The ControlLogix 1756-RIO module connects a ControlLogix processor to a
remote I/O network.

The module can act as a scanner or as an adapter on the network. For additional
information, see publication

1756-UM534

.

1756-RIO Module as a Scanner

As a scanner, with one remote I/O channel, the 1756-RIO module scans I/O on
a remote I/O network.

The module supports the following:

All remote I/O baud rates: 57.6, 115.2, 230.4 Kbaud

Rack numbers from 0…76 octal

All combinations of partial racks

Up to 32 physical adapters

To support 32 physical adapters, you must use an 82  resistor; 150 
resistors allow only 16 adapters.

Block transfers at all possible locations

The module can update block transfers (BTs) automatically via the 1756-RIO
module or can be controlled by the ControlLogix controller. It transfers all I/O
via produced/consumed connections over the backplane to the controller.

IMPORTANT

This module is shipped in scanner mode, with a blank
configuration.

Advertising