20 ControlLogix Remote I/O (RIO) Module

Rockwell Automation Publication 1756-IN610B-EN-P - November 2010

Adapter Mode

This table shows status in order of priority, highest first.

CLX Status Indicator – ControlBus Status

The CLX indicator displays the status of communication with the ControlLogix
processor.

Indicator

Status

Description

RIO

Red

A frame-receive error has been received in the last
second (CRC error, abort, or time-out). Indicator stays
red for one second after the error occurs.

Flashing red/off

One or more racks are not being scanned.

Flashing green/off

Configuration mismatch on one or more racks.

Green

All racks are being scanned and there are no
configuration mismatches.

Indicator

Status

Description

CLX

Green

The module has successfully processed a request
from the ControlBus backplane within the last five
seconds. All required connections are open.

Flashing green/off

Controlling Connection is open, but not all required
connections are open.

Yellow

Idle, no requests received from the backplane in the
last five seconds. No connections; empty
configuration.

Flashing yellow/off

Controlling Connection is not open.

Red

The module has returned a CIP error to a request from
the backplane within the last second. All required
connections are open.

Flashing red/off

The module has returned a CIP error within the last
second. All required connections are not open.