Indicator status for modules – Rockwell Automation 1738-IT2IM12 ArmorPoint RTD and Thermocouple Modules, Series A User Manual

Page 11

Advertising
background image

ArmorPOINT RTD and Thermocouple Input Modules 11

Publication 1738-IN005B-EN-E - January 2013

Network status Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Flashing green

Device is online but has no connections in the established state.

Green

Device is online and has connections in the established state.

Flashing red

One or more I/O connections are in timed-out state.

Red

Critical link failure – failed communication device. Device detected
error that prevents it from communicating on the network. Possible
duplicate MAC ID or baud rate mismatch.

Flashing red/green Communication faulted device – the device has detected a

network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request – long protocol message.

I/O status

Off

Module in CAL mode.

Solid green

Normal (channel scanning inputs).

Flashing green

Channel being calibrated.

Solid red

Major channel fault.

Flashing red

Channel at end of range (over or under).

Indicator Status for Modules