8 ArmorPOINT RTD and Thermocouple Input Modules

Publication 1738-IN005B-EN-E - January 2013

Communicate with the Module

I/O messages are sent to (consumed) and received from (produced) the ArmorPOINT
I/O modules. These messages are mapped onto the processor’s memory. The
ArmorPOINT RTD I/O input module produces 6 Bytes of input data (scanner Rx –
status) and fault status data. The ArmorPOINT thermocouple I/O input module
produces 8 Bytes of input data (scanner Rx – status) and fault status data. They do not
consume I/O data (scanner Tx).

Default Data Map – 1738-IR2M12

Message size: 6 Bytes

15 14 13

12 11 10 09 08 07 06 05

04 03 02 01 00

Produces
(scanner Rx)

Input channel 0 high byte

Input channel 0 low byte

Input channel 1 high byte

Input channel 1 low byte

Status byte for channel 1

Status byte for channel 0

OR

UR

HHA LLA HA

LA

CM CF

OR

UR

HHA LLA HA

LA

CM CF

Consumes
(scanner Tx)

No consumed data

Where:

OR = Overrange; 0 = No error, 1 = Fault

UR = Underrange; 0 = No error, 1 = Fault

HHA = High/High Alarm; 0 = No error, 1 = Fault

LLA = Low/Low Alarm; 0 = No error, 1 = Fault

HA = High Alarm; 0 = No error, 1 = Fault

LA = Low Alarm; 0 = No error, 1 = Fault

CM = Calibration Mode; 0 = Normal, 1 = Calibration mode

CF = Channel Fault Status; 0 = No error, 1 = Fault