12 ArmorPOINT RTD and Thermocouple Input Modules

Publication 1738-IN005B-EN-E - January 2013

Specifications

ArmorPOINT RTD and Thermocouple Input Modules –
1738-IR2M12, 1738-IT2IM12

Attribute

Value

Inputs per module

1738-IR2M12 – 2 single-ended, nonisolated

1738-IT2IM12 – 2 differential, individually isolated

Resolution

1738-IR2M12 – 16 bits, 9.5 mV/cnt, 0.03 °C/cnt (Pt385 @ 25 °)

1738-IT2IM12 – 15 bits plus sign, 2.5 mV/cnt

Thermocouple type (and
resolution average over span)

1738-IT2IM12 only

Sensor

Range

Resolution (average over span)

Type B

30…1820 °C

3 counts/°C

Type C

0…2315 °C

6 counts/°C

Type E

-270…1000 °C

24 counts/°C

Type J

-210…1200 °C

21 counts/°C

Type K

-270…1372 °C

13 counts/°C

Type N

-270…1300 °C

11 counts/°C

Type R

-50…1768.1 °C

4 counts/°C

Type S

-50…1768.1 °C

4 counts/°C

Type T

-270…400 °C

15 counts/°C

RTD sensors supported

1738-IR2M12 only

100

Ω

Pt

α

= 0.00385 Euro (-200…870 °C)

200

Ω

Pt

α

= 0.00385 Euro (-200…630 °C)

100

Ω

Pt

α

= 0.003916 U.S. (-200…630 °C)

200

Ω

Pt

α

= 0.003916 U.S. (-200…630 °C)

10

Ω

Cu

α

= 0.00427 (-200…260 °C)

100

Ω

Ni

α

= 0.00618 (-60…250 °C)

120

Ω

Ni

α

= 0.00672 (-60…250 °C)

120

Ω

Ni

α

= 0.00618 (-60…250 °C)

Cold junction
compensation range

1738-IT2IM12 – 0…70 °C

Input range

1738-IR2M12 – 0…600

Ω

1738-IT2IM12 – ±75 mV

Absolute accuracy

(1)

0.1% full scale @ 25 °C

Accuracy drift w/temp

30 ppm/°C

Advertising