General Specifications

Attribute

Value

Mounting base screw torque

M4 (#8) screw,

0.85 Nm (7.5 lb-in.) in aluminum, 1.8 Nm (16 lb-in.) in steel

Calibration

Factory-calibrated

POINTBus current

1738-IR2 – 220 mA @ 5V DC

1738-IT2I – 175 mA @ 5V DC

Power dissipation, max

1.0 W

Thermal dissipation, max

3.3 BTU/hr

Isolation voltage

Tested at 50V rms (1738-IT2I has isolation between individual
channels)

Dielectric test

1000V rms flash for 1s

External DC power

No external power required

LED indicators

1 green/red – module status indicator, logic side

1 green/red – network status indicator, logic side

2 green/red – input status indicators, logic side

Dimensions, HxWxD

31.75 x 66.80 x 107.95 mm

(1.25 x 2.63 x 4.25 in.)

Weight

0.289 kg (0.637 lb)

Enclosure type rating

Meets IP65/66/67 (when marked)

Wiring category

(1)

1 – on signal ports

Keyswitch position

6

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…60 °C (-4…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):

5…95% noncondensing