Rockwell Automation 1738-IT2IM12 ArmorPoint RTD and Thermocouple Modules, Series A User Manual

Page 9

Advertising
background image

ArmorPOINT RTD and Thermocouple Input Modules 9

Publication 1738-IN005B-EN-E - January 2013

Default Data Map – 1738-IT2IM12

Message size: 6 Bytes

15 14 13

12 11 10 09 08 07 06 05

04 03 02 01 00

Produces
(scanner Rx)

Input channel 0 high byte

Input channel 0 low byte

Input channel 1 high byte

Input channel 1 low byte

Status byte for channel 1

Status byte for channel 0

OR

UR

HHA LLA HA

LA

CM CF

OR

UR

HHA LLA HA

LA

CM CF

OR

UR

Cold junction temperature

(Selectable channel 0, channel 1, or average of both channels 0 and 1)

Consumes
(scanner Tx)

No consumed data

Where:

OR = Overrange; 0 = No error, 1 = Fault

UR = Underrange; 0 = No error, 1 = Fault

HHA = High/High Alarm; 0 = No error, 1 = Fault

LLA = Low/Low Alarm; 0 = No error, 1 = Fault

HA = High Alarm; 0 = No error, 1 = Fault

LA = Low Alarm; 0 = No error, 1 = Fault

CM = Calibration Mode; 0 = Normal, 1 = Calibration mode

CF = Channel Fault Status; 0 = No error, 1 = Fault