Some points to remember, Some points to remember -3 – Rockwell Automation 1756-NEX Nexus Module  User Manual

Page 15

Advertising
background image

About the 1756-CLX/C Module 1-3

Publication 1756-UM524B-EN-P - December 2008

Some Points to Remember

Remember the following points about the 1756-CLX/C module:

• the module is not supported by RSLinx or RSNetworx software
• the module does not support bridging between NeXUS and ControlNet, DeviceNet,

EtherNet/IP, or any other network

• the module does not support bridging between NeXUS sub-nets (i.e., bridging

between 1756-CLX/C modules located in the same chassis)

• the maximum NeXUS (ADP) message size is 1024 bytes
• data rate is 10Mb/sec.; maximum data rate is 100Mb/sec.
• minimum module data transfer rate is 10 packets/sec.
• the module supports a maximum of 32 TCDs
• one Logix controller can own only one 1756-CLX/C module

ATTENTION

Use only the Ethernet connector on the module. Do not use other
connectors.