Use the led status indicators, Use the led status indicators -2 – Rockwell Automation 1756-NEX Nexus Module  User Manual

Page 42

Advertising
background image

5-2 Status Indicators and Troubleshooting

Publication 1756-UM524B-EN-P - December 2008

Use the LED Status Indicators

The 1756-CLX/C module has the following LED status indicators. Use these indicators to
troubleshoot module status.:

Table 5.A LED Status Indicators

This LED

When

Means

So you should

BAT (RED)

ON

The battery is low.

Replace the module.

The battery is charging. The BAT

LED turns OFF within a few

minutes after power is applied.

Wait for the battery to finish

charging.

OFF

The Battery is charged.

The module is not powered up.

Do nothing. The module is ready

for use.

Apply power to the module.

USR

(GREEN)

ON/OFF

Data is being sent or received

over the NeXUS port.

Do nothing. The module is

operating correctly.

OFF

No data is being sent or received

over the NeXUS port.

The module is not powered up.

Check the Communication port

LEDs. If:

• LEDs are working properly,

restart the module

• LEDs are not working

properly, follow the

instructions in Table 5.B on

page 5-3

• the problem persists, replace

the module

Apply power to the module.

OK

(STATUS)

GREEN

The module is operating

correctly.

Do nothing. The module is ready

for use.

RED

The module has experienced an

error.

Restart the module. If the

problem persists, replace the

module.

OFF

The module is not powered up.

Apply power to the module.

Advertising