Table 5.d firmware error codes, Table 5.e module error codes – Rockwell Automation 1756-NEX Nexus Module  User Manual

Page 44

Advertising
background image

5-4 Status Indicators and Troubleshooting

Publication 1756-UM524B-EN-P - December 2008

Table 5.D Firmware error codes

Error type Error

contents

Alpha-

numeric

display

NX46_

System

error

NX60_

System

error code

NX63_

status

level

NX64_

Status

code

NX61_

Send

error code

VX62_

Receive

error code

Event

log

source

User

action

Configu-

ration Error

Configuration

Error

ERR

ON

Error_

Code

N/A

N/A

N/A

N/A

NX SAM

See

Table 5.E

System

Online

Error

NX DLINK is

inactive

ERR

ON

0x11008000 E

0x11008000 N/A

N/A

NXDlink

Major Fault

Data Buffer

Overflowed

RUN

OFF

N/A

W

0x11008001 N/A

N/A

NXDlink

Warning

Data Buffer

Upper Limit

RUN

OFF

N/A

E

0x11008002 N/A

N/A

NXDlink

Minor Fault

Data Buffer

Lower Limit

RUN

OFF

N/A

I

0x11008003 N/A

N/A

NXDlink

Informa-

tion

Receive Limit

Over

of Data Handle

RUN

OFF

N/A

W

0x12008004 N/A

N/A

N/A

Warning

MC Receive

Number

has missed

RUN

OFF

N/A

I

0x11008004 N/A

N/A

NXDlink

Informa-

tion

CPU Temp Over

Limit

RUN

OFF

N/A

W

0x4e000001 N/A

N/A

NX SAM

Warning

CPU Temp

Upper Limit

RUN

OFF

N/A

E

0x4e000002 N/A

N/A

NX SAM

Minor Fault

Send/

Receive

Error

CPU Temp

Lower Limit

RUN

OFF

N/A

I

0x4e000003 N/A

N/A

NX SAM

Informa-

tion

Send Error

Receive Error

RUN

OFF

N/A

N/A

N/A

See Table 5.F

NXDlink

Individ-

ual error for

each handle.

See

Table 5.F.

Module

stopped

STOP

OFF

N/A

N/A

N/A

N/A

N/A

N/A

Table 5.E Module error codes

No. Error code

Decription

User action

1

0x00000001

Incorrect Data Setting for

NX00_Node_Name_param

Correct the Data Setting for

NX00_Node_Name_param

2

0x00000002

Incorrect Data Setting for

NX01_IP_Address_Param

Correct the Data Setting for

NX01_IP_Address_Param

3

0x00000003

Incorrect Data Setting for

NX02_Subnet_Mask_Param

Correct the Data Setting for

NX02_Subnet_Mask_Param

4

0x00000004

Incorrect Data Setting for

NX03_Node_Param[0] “Logical

Node Number”

Correct the Data Setting for

NX03_Node_Param[0]

5

0x00000005

Incorrect Data Setting for

NX03_Node_Param[1] “Local Data

Field Number”

Correct the Data Setting for

NX03_Node_Param[1]

Advertising