Rockwell Automation 1734-8CFGDLX POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix IN User Manual

Page 14

Advertising
background image

14 POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix

Publication

1734-IN039A-EN-P - March 2009

You can select other produced assemblies:

Produced assembly instance 4 is the first byte of produced assembly
instance 101 (Data [0]).

Produced assembly instance 111 is the first eight bytes of produced
assembly instance 101 (Data [0]…[7]).

In RSLogix5000, the default tags will be:

AdapterName:SlotNumber:I.Data

AdapterName:SlotNumber:I.LogicDefinedData

AdapterName:SlotNumber:I.Status.LogicEnabled

AdapterName:SlotNumber:I.Status.Owned

AdapterName:SlotNumber:I.PeerMissing

AdapterName:SlotNumber:I.LogicDefinedIntData[0...7]

Data [16]

Produce Network Analog Word 6

Data [17]

Data [18]

Produce Network Analog Word 7

Data [19]

Where:

Pt = state of the output point,

PNB = Produce Network Bit,

PM = Peer Missing (each bit represents the presence of a configured peer)

Owned = Owned by a master.

When set to 0, the module is producing data without a master.

When set to 1, the module is producing while being owned by a master.

LogicEn = Logic Enabled (0 = logic disabled, 1 = logic enabled)

Default Data Map - Produced Assembly Instance 101 (Continued)

Message Size: 20 Bytes