Rockwell Automation 1734-8CFGDLX POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix IN User Manual

Page 25

Advertising
background image

POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix 25

Publication

1734-IN039A-EN-P - March 2009

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature,
non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):

-40…85°C (-40…185°F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz