Prevent electrostatic discharge, About the module, Prevent electrostatic discharge about the module – Rockwell Automation 1734-8CFGDLX POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix IN User Manual

Page 4

Advertising
background image

4 POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix

Publication

1734-IN039A-EN-P - March 2009

Prevent Electrostatic Discharge

About the Module

The 1734-8CFGDLX module is an 8-point 24V DC I/O module with 8
self-configuring points and DeviceLogix capabilities. Each of the I/O points
can be a DC input or output.
The module supports removal and insertion under power, auto-address, and
auto-baud in compliance with the POINTBus backplane.

ATTENTION

This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines when
you handle this equipment.

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

Use a static-safe workstation, if available.

Store the equipment in appropriate static-safe packaging when not in
use.

ATTENTION

POINT I/O is grounded through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assure proper grounding. The use of other
DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize,
or are poor conductors, can result in improper or intermittent grounding.

Secure DIN rail to mounting surface approximately every 200 mm (7.87 in.) and
use end-anchors appropriately.

ATTENTION

To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

Advertising