18 POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix

Publication

1734-IN039A-EN-P - March 2009

Data [38]

Peer 5 - EPR (ms)

Data [39]

Data [40]

Peer 6 - Slot/MacID

Data [41]

Peer 6 - Consume Message Length (bytes)

Data [42]

Peer 6 - EPR (ms)

Data [43]

Data [44]

Peer 7 - Slot/MacID

Data [45]

Peer 7 - Consume Message Length (bytes)

Data [46]

Peer 7 - EPR (ms)

Data [47]

Where:

Filter = 0 to 65535

μ

s (1000 = default)

FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)

FltV = Fault Value (0 = OFF (default), 1 = ON)

IdlM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)

IdlV = Idle Value (0 = OFF (default), 1 = ON)

RACK = Produce with Rack Assembly 4 and Consume Rack Assembly 34

(0 = Disabled (default), 1 = Enabled)

CFO = DeviceLogix Communication Fault Override of Outputs

1 = Enabled. When enabled, the DeviceLogix program will continue to control the
outputs even in the event of a communication fault.

0 = Disabled (default). When disabled, the outputs will follow the Fault and Idle
settings.

DM = Dependent Mode

MP = Masterless Produce

0 = Disabled (default), 1 = Enabled. When enabled, the module will begin producing
data at powerup and after a connection with a controller is terminated.

Data Map - Configuration Assembly Instance 123 (Continued)

Message Size: 48 Bytes