12 Thermocouple/mV Isolated Input Module

Publication 1746-QS002B-EN-P - July 2002

7. At the source-end of cables from mV devices (see following figure):

remove the drain wire and foil shield

apply shrink wrap as an option

connect to mV devices keeping the leads short

Configure the Software

With your programming software already loaded and your computer set for off-line
programming:

1. Identify the type of SLC processor and operating sytstem on the PROG

DIRECTORY FOR PROCESSORS screen.

2. With the SLC system installed and wired, us the READ CONFIG feature and

follow the prompts to configure the I/O.

3. Enter the rack configuration.

4. Select the type of module in each slot. If 1746-INT4 is not listed, enter ID

code 3515 for OTHER at the bottom of the list.

5. Exit and save to file.

IMPORTANT

IMPORTANT

If noise persists, try grounding the opposite end of the cable.
Ground one end only.

Wires

3/8

Make unshielded wires as
short as possible.

Limit braid length to 12” or
less. Solder braid to lug on
bottom row of I/O chassis

Connect I/O chassis
bolt to earth ground

Solder drain wires to
braid at casing.

Make unshielded wires as short as possible.

3/8

Signal
Wires

Terminal Block

Chnl 0

Chnl 1

Chnl 2

Chnl 3

n/c