Write ladder logic to process input data, Apply power and download your program – Rockwell Automation 1746-INT4 Thermocouple/mV Isolated Input Module Quick Start User Manual

Page 15

Advertising
background image

Thermocouple/mV Isolated Input Module 15

Publication 1746-QS002B-EN-P - July 2002

Write Ladder Logic to Process Input Data

Write ladder logic to process the thermocouple input data for your application:

Apply Power and Download Your Program

Apply power. Download your program to the SLC and put the controller into RUN
mode. In this example, during a normal startup, the module status LED and channel

status 0 LED illuminate.

TIP

For more detailed information on these procedures, refer to
Chapter 7 (Ladder Programming Examples) and Chapter 9
(Application Programming Examples) of the user manual.

TIP

For more detailed information on these procedures, refer to
Chapter 8 (Module Diagnostics and Troubleshooting) of the
user manual.

Channel 1 Data Word

Channel 2 Data Word

Channel 3 Data Word

Output Image

SLC 500 Controller

Data Files

Bit 15

Bit 0

Word 1

Word 2

Word 3

Address

I:1.0

Input Image

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Channel 0 Data Word

Word 0

Word 7

(8 words)

Channel 1 Status Word

Channel 2 Status Word

Channel 3 Status Word

Channel 0 Status Word

(Variable Thermocouple Input Data)

Address

I:1.0
I:1.1
I:1.2
I:1.3

I:1.7

In this example, the module is located in slot 1.

0

1

2

3

INPUT

Channel
LEDs

Module Status
LED

MODULE STATUS

THERMOCOUPLE/mV

CHANNEL

STATUS

ISOLATED

If channel LED is blinking:
Module detected: and status word:

open circuit
under range
over range
config error

bit 12 = 1
bit 13 = 1
bit 14 = 1
bit 15 = 1