Install the module and connect the thermocouples – Rockwell Automation 1746-INT4 Thermocouple/mV Isolated Input Module Quick Start User Manual

Page 5

Advertising
background image

Thermocouple/mV Isolated Input Module 5

Publication 1746-QS002B-EN-P - July 2002

Insert/remove the module into/from the I/O chassis
(slot 1 in this example procedure).

card
guide

module release,
top and bottom

Connect thermocouple wires to channels 0-3.
We show an example for channel 0. Make sure
both cold junction compensation (CJC) devices
are securely attached with correct polarity.

CHL 0±

CJC A
Device

CHL 0+

Thermocouple Wire

Terminal Block

CHL 1+

CHL 1±

Important:
Ground all thermocouple shields
to earth ground at I/O chassis
with 3/8º braid wire. See User
Manual, figure 3.2.

+

±

Important:
Thermocouple inputs are highly
susceptible to electrical noise.
To minimize interference:

Place processor and I/O chassis

in an industrial enclosure.

± Keep signal wires as far from

power and load lines as possible.

Use shielded, twisted-pair

thermocouple extension wire.

Ground each shield only at one end.
Use correct thermocouple polarity.
Keep all unshielded leads short.
Connect the terminal block GND

(#18) to nearest I/O chassis mtg.
bolt with 12 gauge stranded wire.

Install the Module and Connect the Thermocouples

To install your module into the chassis:

1. Turn off the chassis power supply.

WARNING

!

If you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.

WARNING

!

If you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.