Troubleshoot the module – Rockwell Automation 1746-INT4 Thermocouple/mV Isolated Input Module Quick Start User Manual

Page 16

Advertising
background image

16 Thermocouple/mV Isolated Input Module

Publication 1746-QS002B-EN-P - July 2002

Troubleshoot the Module

Monitor the status of input channel 0 to determine its configuration setting and
operational status. This is useful for troubleshooting when the flashing channel LED
indicates that an error has been flagged. If the module status LED is off, or if the

channel 0 LED is off or flashing, refer to step 8.

TIP

For more detailed information on these procedures, refer to
Chapter 8 (Module Diagnostics and Troubleshooting) of the
user manual.

Channel 1 Data Word

Channel 2 Data Word

Channel 3 Data Word

Output Image

SLC 500 Controller

Data Files

Bit 15

Bit 0

Word 1

Word 2

Word 3

Address

I:1.4

Input Image

Channel 0 Data Word

Word 0

Word 7

(8 words)

Channel 1 Status Word

Channel 2 Status Word

Channel 3 Status Word

Channel 0 Status Word

0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0

Input

T

ype

Data Format

Open Circuit

T

ype

T

emperature Units

Zero (not used)

Channel Status

Open Circuit Error

Under Range Error

Over Range Error

Configuration Error

For this example, during normal operation only bit 11 is set.