Channel configuration worksheet, Project, Project ________________________ slot number – Rockwell Automation 1746-INT4 Thermocouple/mV Isolated Input Module Quick Start User Manual

Page 19: Slot number _____ channel number, Channel number

Advertising
background image

Thermocouple/mV Isolated Input Module 19

Publication 1746-QS002B-EN-P - July 2002

Channel Configuration Worksheet

SLC is a registered trademark of Rockwell Automation, Inc.
Allen-Bradley and SLC 500 are trademarks of Rockwell Automation, Inc.

Channel Configuration Word (O:e.0 through O:e.3) - Bit Descriptions

Set these bits in the Channel Configuration Word

Bit(s)

Define

To Select

15-12

11

10

9

8

7

6

5

4

3

2

1

0

Description

TC Type J

0

0

0

0

TC Type K

0

0

0

1

TC Type T

0

0

1

0

TC Type E

0

0

1

1

Project ________________________

TC Type R

0

1

0

0

Project ________________________
Slot Number _____

TC Type S

0

1

0

1

Slot Number _____
Channel Number _____

TC Type B

0

1

1

0

Channel Number _____

Input

TC Type N

0

1

1

1

0-3

Input
Type

50mV

1

0

0

0

100mV

1

0

0

1

Configure the channel for the input type connected to it.

TC Type C

1

0

1

0

Valid inputs are thermocouples and analog input signals
of

+

50mV and

+

100mV. You can configure the channel to

TC Type D

1

0

1

1

of

+

50mV and

+

100mV. You can configure the channel to

read the cold-junction (CJC) temperature. When reading

Invalid

1

1

0

0

the CJC temperature, the channel ignores the physical
input signal.

Invalid

1

1

0

1

input signal.

Invalid

1

1

1

0

CJC Temp.

1

1

1

1

Engr. Units x1

0

0

Select the channel data format from:
Engineering units (EU) x1 or x10

Data

Engr. Units x10

0

1

Engineering units (EU) x1 or x10
For EU x1, values are in 0.1 degrees or 0.01mV.
For EU x10, values are in whole

o

C or

o

F or 0.1mV.

4, 5

Data

Format

Scaled-for-PID

1

0

For EU x10, values are in whole C or F or 0.1mV.
Scaled-for-PID (value is the same for any input type)
Proportional input signal range is scaled to 0-16,383 counts.

Counts

1

1

Proportional input signal range is scaled to 0-16,383 counts.
Proportional counts (value is same for any input type)
Proportional input signal range is scaled to

+

32,767 counts.

Zero

0

0

Select module response to a detected open circuit from:
Zero
to force the channel data word to zero.

Open

Upscale

0

1

Zero to force the channel data word to zero.
Upscale to force the channel data word to full scale.
Downscale to force channel data word to low scale.

6, 7

Circuit

Mode

Downscale

1

0

Downscale to force channel data word to low scale.
Important: A bit selection or 1 1 is invalid.
For an open CJC thermistor, mV channels are not affected.

Invalid

1

1

For an open CJC thermistor, mV channels are not affected.
Important: The module requires 500 msec or one module
update to flag the error while it ramps the channel input.

Units

Degrees C

0

Select

5

C/

5

F for thermal inputs. Ignored for mV inputs.

5

5

8

o

F,

o

C

Degrees F

1

Important: For EU x1 and

5

F (0.1

5

F), an over-range error

will occur above 3276.7

5

F (cannot exceed 32767 counts).

9, 10

Unused

Unused

0

0

These bits must be zero for a valid configuration.

Chnl

Channel Off

0

11

Chnl

Enable

Channel On

1

12-15

Unused

Unused

0000

These bits must be zero for a valid configuration.

Enter Your Bit Selections >>

0000

For the Channel Configuration Word

Disable unused channels for faster response.
When set, module configures the channel and reads channel input before setting this bit in status word.
If you change the configuration word, the status word must reflect the change before new data is valid.
If you clear configuration word, module clears channel and status words. For new configuration word,
channel data and status words remain cleared until the module sets this bit (11) in the status word.