Power supply requirement – Rockwell Automation 2706-DXX Dataliner Message Display DL5 Series User Manual

Page 92

Advertising
background image

2706-UM001A-US-P

12-4

Installation Instructions

Power Supply Requirement

The power supply used to power the DL5 and to supply the parallel port
data lines must meet the following specifications:

Supply Voltage:

12-24 VDC

Ripple:

5% of input voltage p-p (max.)

Noise:

5% of input voltage p-p (max.)

Supply Current

12 VDC

250 mA operating (300 mA inrush)

24 VDC

125 mA operating (300 mA inrush)

Parallel Port: (17 inputs maximum)

5 VDC

3.0 mA per input (typical)

12 VDC

7.3 mA per input (typical)

24 VDC

14.6 mA per input (typical)

Fusing:

External fusing should be provided.

After the DL5 has been mounted, the necessary wiring can be connected to
the DL5. The following figure illustrates the terminal connections located
on the back of the DL5. Perform the following steps to connect wiring to
the DL5.

!

ATTENTION: To avoid system ground loops and damage to
equipment, the same power supply must be used for the parallel
port and the power input to the DL5.