Wire Sizing Based
on Ambient Temperature

Find the 90°C aluminum wire size
needed to connect a 47,700 volt-amp
load to a 240 volt, single-phase source.

Steps Keystrokes Display

Clear calculator

[On/C] [On/C]

0.

Set to 1-phase

[Set] 1

1 PH

Set to 90°C

[Set] 9

1 Ø 90 Cu 1 PH

Set to alum.

[CU/AL]

1 Ø 90 Al 1 PH

Enter volt-amps

47700 [VA]

47,700. VA

Enter volts

240 [Volts]

240. VOLT

Find amps

[Amps]

198.75 AMPS

Find wire size

[WireSz]

0000 AL

AWG WIRE SIZE

What is the adjusted wire size, if the
ambient temperature rating is changed
from the default 30°C to 40°C?

Change ambient
temperature

40 [Set] [2]

AMB° 40

Û&

Find adjusted
wire size

[WireSz]

250 AL

AWG WIRE SIZE

NOTE: Ambient temperature will remain at 40°C
unless you change it or perform an ALL CLEAR
([Set] [x]).