Calculated Industries 5025 User Manual

Page 35

Advertising
background image

User's Guide — 33

Steps Keystrokes Display

Enter wire size

8 [WireSz]

8 CU

AWG WIRE SIZE

Solve volt. drop

[VD%]

3.0 DROP V

Solve % v.drop

[VD%]

1.4 DROP V %

Finding Three-Phase
Voltage Drop

A 20-amp three-phase load is being fed
by a 230-volt source located 150 feet
away. The installation specifications
require 75°C #10 THW stranded copper
conductor. What is the voltage drop on
this branch circuit?

Steps Keystrokes Display

Reset calculator

[Set] [x]

0.

Set to 75°C

[Set] 7

3Ø 75 Cu 0.

Enter amps

20 [Amps]

20. AMPS

Enter volts

230 [Volts]

230. VOLT

Enter length(feet) 150 [Length]

150. FEET

Enter VD wire size10 [WireSz]

10 CU

AWG WIRE SIZE

Find VD

[VD%]

6.4 DROP V

Find VD%

[VD%]

2.8 DROP V %