30 — ElectriCalc LT

Sizing Temperature-Adjusted
Derated Wires

A circuit was built with 90°C aluminum
wire connecting a 47,650 volt-amp load
to a 240 volt, single-phase source. Am-
bient temperature is 50°C. What is the
derated wire size required if eight cur-
rent-carrying THHN wires were installed
in the raceway?

Steps Keystrokes Display

Reset calculator

[Set] [x]

0.

Set to 1-phase

[Set] 1

1 PH

Set to 90°C

[Set] 9

1Ø 90 Cu 1 PH

Toggle to alum.

[CU/AL]

1Ø 90 Al 1 PH

Enter volt-amps

47650 [VA]

47,650. VA

Enter volts

240 [Volts]

240. VOLT

Set to 50°C amb 50 [Set] [2]

AMB° 50

Û &

Find adjst wire sz. [WireSz]

300 AL

AWG WIRE SIZE

Find derated

8 [Set] [ParSz]

500 AL

wire size

D/R WIRE SIZE

NOTE: Ambient temperature should be
changed back to 30°C to avoid conflicts
in answers through out the rest of this
manual.

Reset to 30°C

30 [Set] [2]

AMB° 30

Û &