Calculated Industries 5025 User Manual

Page 37

Advertising
background image

User's Guide — 35

Finding Voltage Drop Distance

How far from a single-phase 240-volt
source can you install a 15 amp load
using 60°C #10 Al branch circuit con-
ductors? Assume a 3% allowable volt-
age drop.

Steps Keystrokes Display

Reset calculator

[Set] [x]

0.

Set to single ph.

[Set] 1

1 PH

Set to aluminum [CU/AL]

1Ø 60 Al 1 PH

Enter amps

15 [Amps]

15. AMPS

Enter volts

240 [Volts]

240. VOLT

Enter wire size

10 [WireSz]

10. AL

AWG WIRE SIZE

Enter 3% VD

3 [VD%]

3. DROP V %

Find distance

[Length] 123.77387 FEET

Find actual
voltage drop

[VD%]

7.2 DROP V

Find % v.drop

[VD%]

3.0 DROP V

NOTE: The calculator automatically
makes adjustments for resistance using
NEC Chap 9, Table 8, if the insulation
type is other than 75°C.